Ep.32 · Case file

An NBA game in Chicago was called off in January 2026 because the floor was sweating.

On Thursday 8 January 2026, the Miami Heat were scheduled to play the Chicago Bulls at the United Center at 7 p.m. Central. The game never started. Players from both teams said the floor was slippery in warm-ups, and arena staff spent the next hour and three quarters pushing large mops across the court and shuffling over it with towels under their feet, while the arena’s cooling was turned up. At 8:53 p.m., after a delay of about 1 hour 46 minutes, the league, the officials and both coaching staffs agreed to postpone. The referee’s explanation was short: they could not guarantee a safe playing surface. Nothing was leaking. The water was coming out of the air.

The United Center is shared by the Bulls and the NHL’s Chicago Blackhawks. The Blackhawks had played there the night before and were due to play again the next night, so the ice sheet was left frozen in place and the basketball floor was laid over it, separated by an insulating deck. That is normal practice in multi-use arenas. What was not normal was the air above it. Outside it was 57°F and raining heavily, unusually warm for a Chicago January. Inside, reports put the bowl above 71°F with relative humidity above 50%, and players said conditions worsened as the building filled.

Condensation is a question of two temperatures. Air at 71°F and 50% relative humidity has a dew point of roughly 52°F: any surface colder than that pulls water out of the air touching it, the same way a cold glass beads on a summer day. A hardwood floor sitting on a frozen slab, with the cold soaking up through the deck, can easily be colder than 52°F at its surface. The bowl’s air circulation then keeps delivering fresh humid air, from the rain-soaked outside air and from thousands of arriving spectators, down onto the court. Each pass leaves a film of water on the maple, which is why mopping could not keep up.

It is also why turning the air conditioning up did not solve it. Cooling the air lowers its temperature, but unless the system is removing moisture it barely moves the dew point, and the dew point is the number the floor responds to. A cooler arena with the same amount of water in its air still condenses on a floor that is colder than that dew point. The NBA has seen the same failure before: per Newsweek, games in Minnesota and Philadelphia were postponed for condensation in the 2016–17 season, and a Trail Blazers–Timberwolves game was delayed in March 2017 by humidity and ice under the court.

The working target comes from rink design. Ice-arena guidance keeps the bowl at a dew point between 32°F and 40°F, usually with desiccant dehumidification, because at that dew point even a surface close to freezing has nothing to condense. Zephyr’s simulation of a bowl with this layout shows both states. With the arena air at a dew point near 52°F, the bowl’s circulation drops humid air onto the centre of the court and spreads it outward along the cold floor, where the surface sits below the dew point and water accumulates across the hardwood. With the bowl air dried to a 38°F dew point and supplied low from slots at the foot of each stand, so that the driest air sweeps across the floor before it mixes into the bowl, the court surface stays above the dew point and the water film does not form.

The lesson extends past basketball. Any building where a cold surface shares a room with occupied, humid air — a rink converted for concerts, a cold-store loading bay, a slab cooled from below — is controlled by the same two numbers: how cold the surface is, and how much water is in the air reaching it. Both are design decisions, and both can be checked before the room is full.

Sources